IEC 類別
|
C1
|
|
|
C2
|
|
|
C3
|
|
|
D1
|
|
額定電壓 UN
|
24 V DC
|
|
最大持續(xù)工作電壓UC
|
30 V DC
|
|
|
21 V AC
|
|
額定電流
|
350 mA (50 °C)
|
|
UC時,有效工作電流IC
|
≤ 10 μA
|
|
殘流IPE
|
≤ 2 μA
|
|
標稱放電電流In (8/20) μs(線芯-線芯)
|
10 kA
|
|
標稱放電電流In (8/20) μs(線芯-地)
|
10 kA (每路徑)
|
|
標稱放電電流In (8/20) μs(屏蔽-地)
|
10 kA (選配)
|
|
脈沖放電電流Iimp (10/350) μs
|
1 kA
|
|
最大放電電流Imax (8/20) μs(線芯-線芯)
|
10 kA
|
|
最大放電電流Imax (8/20) μs(線芯-地)
|
10 kA (每路徑)
|
|
最大放電電流Imax (8/20) μs(屏蔽-地)
|
10 kA
|
|
額定功率脈沖電流lan(10/1000)μs(線芯-線芯)
|
30 A
|
|
額定功率脈沖電流lan(10/1000)μs(線芯-地)
|
100 A (每路徑)
|
|
額定功率脈沖電流lan(10/1000)μs(屏蔽-地)
|
100 A
|
|
輸出電壓限值1 kV/μs(線芯-線芯)波峰
|
≤ 50 V
|
|
輸出電壓限值1 kV/μs(線芯-地)波峰
|
≤ 1.4 kV (直接接地)
|
|
輸出電壓限值1 kV/μs(屏蔽-地)波峰
|
≤ 600 V (選配)
|
|
輸出電壓限值1 kV/μs(線芯-線芯)靜態(tài)
|
≤ 50 V
|
|
輸出電壓限值1 kV/μs(線芯-地)靜態(tài)
|
≤ 1.4 kV (直接接地)
|
|
在In下的殘壓(線芯-線芯)
|
≤ 50 V
|
|
殘壓lan(10/1000)μs(導線-導線)
|
≤ 50 V
|
|
電壓保護水平Up(線芯-線芯)
|
≤ 50 V (C1 - 0.5 kV / 250 A)
|
|
|
≤ 55 V (C1 - 1 kV/500 A)
|
|
|
≤ 55 V (C2 - 2 kV/1 kA)
|
|
|
≤ 55 V (C2 - 10 kV / 5 kA)
|
|
|
≤ 50 V (C3 - 10 A)
|
|
|
≤ 50 V (C3 - 25 A)
|
|
|
≤ 80 V (D1 - 1 kA)
|
|
電壓保護水平Up(線芯-地)
|
≤ 1.4 kV (C1 - 1 kV/500 A)
|
|
|
≤ 1.4 kV (C2 - 2 kV/1 kA)
|
|
|
≤ 1.4 kV (C2 - 10 kV / 5 kA)
|
|
|
≤ 1.4 kV (C3 - 25 A)
|
|
|
≤ 1.4 kV (C3 - 100 A)
|
|
|
≤ 1.4 kV (D1 - 1 kA)
|
|
電壓防護等級Up(屏蔽-接地)
|
≤ 600 V (C1 - 0.5 kV / 250 A)
|
|
|
≤ 650 V (C1 - 1 kV/500 A)
|
|
|
≤ 650 V (C2 - 2 kV/1 kA)
|
|
|
≤ 650 V (C2 - 10 kV / 5 kA)
|
|
|
≤ 650 V (C3 - 10 A)
|
|
|
≤ 750 V (C3 - 25 A)
|
|
|
≤ 750 V (C3 - 100 A)
|
|
|
≤ 650 V (D1 - 1 kA)
|
|
響應時間tA(線芯-線芯)
|
≤ 1 ns
|
|
響應時間tA(線芯-地)
|
≤ 100 ns
|
|
響應時間tA(屏蔽-地)
|
≤ 100 ns
|
|
輸入衰減aE,對稱
|
典型值 0.5 dB (≤ 1 MHz / 50 Ω)
|
|
|
典型值 0.2 dB (≤ 400 kHz / 150 Ω)
|
|
截止頻率fg(3dB),50 Ω 對稱系統(tǒng)
|
典型值 6 MHz
|
|
截止頻率fg(3dB),150 Ω 對稱系統(tǒng)
|
典型值 2.5 MHz
|
|
每條路徑的電阻
|
2.2 Ω ±10 %
|
|
電涌保護故障報警
|
無
|
|
電涌電流電阻(導線-導線)
|
C1 - 1 kV / 500 A
|
|
|
C2 - 10 kV / 5 kA
|
|
|
C3 - 25 A
|
|
|
D1 - 1 kA
|
|
電涌電流電阻(導線-接地)
|
C1 - 1 kV / 500 A
|
|
|
C2 - 10 kV / 5 kA
|
|
|
C3 - 100 A
|
|
|
D1 - 1 kA
|
|
沖擊耐受力(屏蔽-地)
|
C1 - 1 kV/500 A
|
|
|
C2 - 10 kV/5 kA
|
|
|
C3 - 100 A
|
|
|
D1 - 1 kA
|
|
交變電流載流量(線-地)
|
10 A - 1 s
|
|
交變電流載流量(屏蔽-接地)
|
10 A - 1 s
|